Exam Rooms
Download PFD DatasheetFloor Construction
Floors are 100 mm (4") thick with 11 swg cold rolled
steel walking surfaces, 14 swg cold rolled steel
framing members and 16 swg bottom face sheets.
Acoustical filler is high density, incombustible
mineral wool fill with a minimum density of 1.4 kg
per cubic metre (3 lb per cubic foot). The entire
floor floats on vibration isolators and rails.
Isolators are rated with a natural frequency of 6.5
Hz.
Door Construction
Doors are 100 mm (4") thick, of similar construction
to that of the walls and ceiling. Door is flush
mounted on heavy duty cam lift hinges. A double
magnetic gasket sealing system and flush sill seal
design assures the acoustic seal. Standard door is
927 mm x 1918 mm with an opening of 813 mm x 1873 mm
(36-1/2" x 75-1/2" with an opening of 32" x 73-3/4"),
and is of out-swinging design.
Window Construction
Double-glazed 610 mm x 762 mm (24" x 30"). Window is
constructed using 6 mm (1/4") safety glass and is set
in the panel using a viseo-elastic gasket.
Ventilation
Ventilation silencers are wall or ceiling mounted. A
total of two silencers, an intake and exhaust, are
provided for each room. Silencers are designed to
provide up to 250 cfm each with an entrance velocity
of less than 300 cfm. The system will not generate
noise levels in excess of those specified by ANSI S-i
1991 standards.
Electricity and Lighting
Rooms are equipped with at least one double head
incandescent light and one duplex receptacle.
Optional additional lighting and electrical outlets
are available. Electrical service runs inside the
acoustic wall system whenever possible, and is
connected to the outside by way of a surface exterior
mounted electrical box.
Clinical Jack Panel
A pre-wired jack panel is provided with nine (3-wire)
phone jacks, one Cinch Jones 303 and one 304
connector, and a 1" (25 mm) capped pass-through
connection. The panel face is removable and will not
detract from the room's acoustical performance.
Finish
The interior and exterior surfaces are finished with
a durable commercial enamel. The standard colour is
beige, however, custom colours are available.
Noise Reduction
The audiometric room tested in room configuration by
an independent laboratory shall exhibit the following
minimum characteristics when tested per ASTM E596-77.
(i) data subject to change without notice (ii)
Attenuation may vary slightly depending on the
acoustical environment.
Optional Features
• One Way Glass
• Special Paint Colours
• Special Oversize Windows
• Non-Standard Jack Panel
• Extra or Special Lighting
• RF Shielding Package
• Special Paint Colours
• Special Oversize Windows
• Non-Standard Jack Panel
• Extra or Special Lighting
• RF Shielding Package
Acoustic Performance